13
EN
Indicates the ECO mode is enabled.
Indicates the
Inversor
circuit is working.
Indicates the output is working.
Battery information
Indicates the Battery ca
pacity by 0
-
25%, 26
-
50%, 51
-
75%, and 76
-
100%.
Indicates the battery is
not connected.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
3-3. Audible Alarm
Description
Buzzer status
Muted
UPS status
Bypass mode
Beep
ing
once every
2
minutes
Yes
Battery mode
Beep
ing
once every
4
seconds
Fault mode
Beeping continu
ously
Warning
Ove
rload
B
eep
ing
twice every second
No
Low
b
attery
Beeping once every second
Battery unconnected
Over
c
harge
EPO enable
Fan failure
/Over
temp
erature
Charger failure
IP fuse
broken
Over
l
oad
3
times in 30min
EPO
s
tatus
C
over
of maint
ain switch is open
Fault
Bus start failure
Beeping continuously
Yes
Bus over
Bus under
Bus unbalance
Bus
short circuited
Inversor
soft start failure
High
Inversor
voltage
Low
Inversor
voltage
Inversor
output short circuited
Ne
gative power fault
Battery SCR short
circuited
Inversor
relay short
circuited
Battery voltage
loss
Parallel communication fail
ure
Parallel output current unbalance
Over temperature
CPU communication
failure
Overload
Vista de pagina 13