7.UPS is now in the maintenance bypass mode, see below (Note: the Serv disconnect i.e.
battery fuse must be turned off):
Transfer UPS from maintenance bypass mode to normal mode:
1.The normal start position should be following:
When the LED of bypass turns green,the UPS enters into bypass mode.
3.Turn the Maintenance switch to
UPS
side.
2.Turn ON the Bypass Input switch and N switch