25
Use cable cross section and protective device specication
Model VFI 20000TP 3/3 BE/BI
Rectier Input L1, L2, L3, N,
Bypass Input L1, L2, L3, N,
min. conductor cross section[mm ] 6
max. possible cross section[mm ] 35
Rectier Input L1, L2, L3, N breaker (A) 60A 230VAC
Bypass Input L1, L2, L3, breaker (A) 60A 230VAC
Rectier Input fuse (A) 60A 250VAC
Bypass Input fuse (A) 60A 250VAC
Output L1, L2, L3, N,
min. conductor cross section[mm ] 6
max. possible cross section[mm ] 35
External Battery Cabinet Positive
pole(+),Neutral pole,Negative pole (-),
min. conductor cross section[mm ] 10
max. possible cross section[mm ] 35
80A 250VDC
80A 250VDC
Protective Earthing conductor [mm ] Max 35
40A 250V AC Clearance
distances:>=1.4mm Break time<=15s
Torque for xing above terminals 2.8-3 Nm
Internal battery fuse 100A 700VAC
External Battery Cabinet Fuse (A) in
Positive pole(+),Neutral pole,
Negative pole (-),
External Battery Cabinet breaker (A) in Posi-
tive pole(+),Neutral pole,Negative pole (-),
Backfeed protection device
2
2
2
2
2
2
2
Notice!
The following label must be displayed on all switching devices installed in the same
electrical system as the UPS, even when these are located at a distance from the area
in which it is located (according to European standard EN 62040-1-1).