Diagram 3-2-7-3
Refer to the following table 3-2-7-3.
Parameter Value
Battery Mode Audible Warning
Yes – Allow audible warning in battery mode
No – Keep silence in battery mode
Energy Saving Yes – If the load is light, Shut down UPS in 5 minutes
when AC Fail
No – UPS won’t be shut down until battery backup time
exhaust
Auto Reboot UPS When AC
Input Restored
Yes – Auto-restart enable
No – Auto-restart disable
Automatic Self-Test Yes – Automatic self-test enable
No – Automatic self-test disable
Input Type Normal – Accept normal AC line range
Wide range – Accept wide AC line range
Generator – Accept generator’s output
Output Voltage Rating Can be 110V,120V,127V,220V,230V,240V
External battery module
number
Only long time discharged model has this option, the
number is from 00 to 10.
Table 3-2-7-3
For telecom power, Refer to the following diagram 3-2-7-4